This document outlines the specifications for the B1500E3C-AU model from the PowerLink generator series, focusing on design standards, environmental operating conditions, factory inspection, painting process, general features, and equipment specifications.
B1500E3C-AU
Standards & Conditions
- Design Standards:
- Conformite Europeenne (CE)
- ISO8528-5:2005
- AS 3000-2018
- AS 3010-2017
- Environmental Operating Conditions:
- Suitable for indoor or outdoor installation.
- Temperature Range: -25℃ to 45℃ (coolant heater needed below 5℃).
- Humidity: Less than 80%.
- Altitude: Below 1000 meters.
General Features
- Engine and Alternator:
- Baudouin engine 12M33G14D3/5
- Leroy Somer alternator LSA50.2L8
- Control Module: PLC-500.
- Additional Features:
- ABB main circuit breaker (2500A), speed governor (ECU), excitation system (AREP), AVR Model R450.
- Key switch, emergency stop switch, ATS receptacle, 4x12V/150AH batteries.
- Powder-coated canopy, 50℃ radiator, fire extinguisher, oil pump, steel base frame with fork slots, vibration isolators, dry type air filter.
- Fuel tank for 3 hours running, drain points for fuel tank, fuel inlet pump and control box, fuel-water separator.
Equipment Specification
- General Technical Data:
- Model: B1500E3C-AU
- Tank Capacity: 1250L
- Dry Weight: 14984kg
- Noise Level @7m: 82.6dBA
- Dimensions: 6058x2438x2591mm
- Power Ratings: Standby Power 1650kVA/1320kW, Prime Power 1500kVA/1200kW
- Voltage: 380V, 400V, 415V, 440V
- Diesel Engine Specifications:
- Manufacturer: Baudouin, Model: 12M33G14D3/5
- Details including dimensions, weight, number of cylinders, bore, stroke, displacement, compression ratio, injection type, intake system, cooling system, battery voltage, fuel and oil type, capacities, back pressure, power ratings, fuel consumption.
- Alternator Specifications:
- Manufacturer: Leroy Somer, Model: LSA50.2L8
- Specifications include exciter type, cooling fan, windings, insulation class, winding pitch, terminals, drip proof rating, altitude limit, overspeed limit, air flow, voltage regulation, harmonic specifications, telephone interference.
Control System
- PLC-500 Control System:
- Microprocessor-based control unit for genset protection and breaker control.
- Functions include monitoring operational parameters, indicating status and fault conditions, multiple protections, display features, manual/automatic/remote work modes, RS232 & RS485 communication, real-time clock, runtime display, 250 log entries, and load sharing capabilities.